Transmission Elements Outage Report for  30-May-2023
 
A. Details of Transmiss                    ioPlanned Outage n Elements under Planned Outage:-
Sl NoSub-Station/LineCategoryOwner NameOutage DateExpected Revival DateRevival DateReason/Remarks
1OKHLA 220/33kV 100MVA Tx-III220/33kV ICTsDTL10/05/2023 16:1531/05/2023 18:00 GAS FILLING WORK.
2MASJID MOTH 33 KV SIRIFORT33kV FeedersDTL13/05/2023 08:2031/05/2023 18:00 ISOLATOR DAMAGED.
3MASJID MOTH 220/33kV 100MVA Tx-I220/33kV ICTsDTL13/05/2023 11:0531/05/2023 18:00 HOT POINT.
4OKHLA 220/33kV 100MVA Tx-III220/33kV ICTsDTL30/05/2023 08:38 30/05/2023 08:50SF-6 GAS FILLING.
5220kV ROHINI-SHALIMARBAGH CKT-II220 KV LINEDTL10/05/2023 13:5031/05/2023 18:00 AT ROHINI-I : TO ATTEND DAMAGED CONDUCTOR.
6220KV MUNDKA-PEERAGARHI CKT-I220 KV LINEDTL22/05/2023 13:0531/05/2023 18:00 AT PEERAGARHI : CABLE JOINING WORK.
7220kV NARAINA-RIDGE VALLEY CKT-I220 KV LINEDTL30/05/2023 08:38 30/05/2023 08:50SF-6 GAS FILLING.
 
B. Details of Transmission Elements under Forced Outa    ge:-Forced Outage
Sl NoSub-Station/LineCategoryOwner NameOutage DateExpected Revival DateRevival DateReason/Remarks
1SUBZI MANDI 33/11kV, 16MVA Tx-II33/11kV TransformersDTL02/05/2023 20:2531/05/2023 18:00 RYB PHASE, DIFFERENTIAL, 86.
2VASANT KUNJ 220/66kV 160MVA Tx-I220/66kV ICTsDTL03/05/2023 13:4031/05/2023 18:00 ANY TRIP, O/C, B PHASE , 86, E/F.
3VASANT KUNJ 66/11kV, 20MVA Tx-II 66/11kV TransformersDTL30/05/2023 03:42 30/05/2023 19:09O/C
4VASANT KUNJ 66/11kV, 20MVA Tx-II 66/11kV TransformersDTL30/05/2023 19:10 30/05/2023 22:25DIFERENTIAL, RY PHASE.
5220kV WAZIRABAD-GEETA COLONY CKT-I 220 KV LINEDTL17/05/2023 12:0531/05/2023 18:00 At Wazirabad : RYB Phase trip, Auto reclose lock out 86, Start Phase BN, Trip phase BN, Zone-I,II &III, Dist trip, Zone-I. At Geeta Colony: 86, Master Relay, RYB trip, Dist prot, Zone-I, Dist 3.360Km.
C. Details of Transmission Elements Opened manually due t       o H igh Voltage:-